Backflow assembly test · 4492 Orchard Rd

Approved

Filed Aug 22, 2026 by Reese Vance, Valley Backflow Testing · filed from phone

Report

Date of service
Aug 22, 2026
Assembly type
RP
Serial number
A678044
Size
3/4
Test gauge serial
G-1387
Gauge calibration date
Mar 23, 2026
Check valve 1
3.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 003-10-01228
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4492 Orchard Rd
Owner: Jordan Ellery
Parcel 003-10-01228