← Backflow review queue
Backflow assembly test · Two Rivers Self Storage
ApprovedFiled Oct 23, 2026 by Drew Lindqvist, Ridge Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Oct 23, 2026
- Assembly type
- RP
- Serial number
- W546474
- Size
- 1
- Test gauge serial
- G-5813
- Gauge calibration date
- Jul 20, 2026
- Check valve 1
- 3.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Relief valve opened at
- 4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 003-73-01083
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
1368 Old Church Rd
Owner: Marsh Holdings LLC
Parcel 003-73-01083