Backflow assembly test · 567 Fox Run Trl
ApprovedFiled Nov 2, 2026 by Blake Harlow, Ridge Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Nov 2, 2026
- Assembly type
- DC
- Serial number
- W353151
- Size
- 3/4
- Test gauge serial
- G-4197
- Gauge calibration date
- Dec 2, 2025
- Check valve 1
- 0.5 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.7 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 003-65-01012
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.