New Castle County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 7678 Orchard Dr

Approved

Filed May 31, 2026 by Reese Vance, Valley Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
May 31, 2026
Assembly type
RP
Serial number
W584081
Size
3/4
Test gauge serial
G-7188
Gauge calibration date
Nov 8, 2025
Check valve 1
5.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 003-52-01190
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7678 Orchard Dr
Owner: Riley Ramirez
Parcel 003-52-01190