Backflow assembly test · 7098 Mill Creek Trl

Approved

Filed Aug 20, 2026 by Reese Vance, Valley Backflow Testing · filed from phone

Report

Date of service
Aug 20, 2026
Assembly type
PVB
Serial number
W623904
Size
3/4
Test gauge serial
G-5721
Gauge calibration date
Jan 30, 2026
Check valve 1
6.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 003-15-01175
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.