Sussex County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Station Pizza

Approved

Filed May 29, 2026 by Cameron Lindqvist, Heritage Plumbing & Backflow · filed from phone

Report

Date of service
May 29, 2026
Assembly type
RP
Serial number
Z273334
Size
1
Test gauge serial
G-8158
Gauge calibration date
Jan 4, 2026
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 005-74-01104
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3626 Hickory Trl
Owner: Pruitt Holdings LLC
Parcel 005-74-01104