← Backflow review queue
Backflow assembly test · Maple Leaf Bakery
ApprovedFiled Aug 5, 2025 by Jordan Ellery, Patriot Backflow Testing · filed from phone
Report
- Date of service
- Aug 5, 2025
- Assembly type
- RP
- Serial number
- A408283
- Size
- 1 1/2
- Test gauge serial
- G-8711
- Gauge calibration date
- Dec 29, 2024
- Check valve 1
- 7.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 005-58-01234
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
631 Fox Run Ct
Owner: Ellery Holdings LLC
Parcel 005-58-01234