Sussex County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 2406 Laurel Trl

Approved

Filed Apr 7, 2026 by Alex Calloway, Ridge Plumbing & Backflow · filed from phone

Report

Date of service
Apr 7, 2026
Assembly type
RP
Serial number
K630759
Size
3/4
Test gauge serial
G-9550
Gauge calibration date
Jan 29, 2026
Check valve 1
9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 005-22-01167
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2406 Laurel Trl
Owner: Avery Whitcomb
Parcel 005-22-01167