Backflow assembly test · Two Rivers Apartments
ApprovedFiled Oct 31, 2026 by Reese Danner, Heritage Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Oct 31, 2026
- Assembly type
- RP
- Serial number
- W246948
- Size
- 1 1/2
- Test gauge serial
- G-6870
- Gauge calibration date
- Sep 22, 2026
- Check valve 1
- 6.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.8 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-81-01189
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4341 Stone Gate Rd
Owner: Lindqvist Holdings LLC
Parcel 001-81-01189