Backflow assembly test · 300 Cedar Hollow Ln
ApprovedFiled Feb 9, 2026 by Reese Danner, Heritage Plumbing & Backflow · filed from phone
Report
- Date of service
- Feb 9, 2026
- Assembly type
- RP
- Serial number
- Z692899
- Size
- 3/4
- Test gauge serial
- G-8024
- Gauge calibration date
- Jul 25, 2025
- Check valve 1
- 5.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-36-01101
- Readings in range, no flags
- Result: passing. Next due date resets when approved.