Backflow assembly test · 5857 Stone Gate Ct
ApprovedFiled Oct 18, 2025 by Jamie Wexler, Summit Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Oct 18, 2025
- Assembly type
- DC
- Serial number
- B946207
- Size
- 3/4
- Test gauge serial
- G-7015
- Gauge calibration date
- May 2, 2025
- Check valve 1
- 7.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-25-01043
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
5857 Stone Gate Ct
Owner: Sam Ellery
Parcel 001-25-01043