Backflow assembly test · 783 Quarry Dr

Approved

Filed Dec 26, 2024 by Logan Marsh, Evergreen Backflow Testing · filed from phone

Report

Date of service
Dec 26, 2024
Assembly type
RP
Serial number
A340361
Size
1
Test gauge serial
G-9421
Gauge calibration date
Sep 27, 2024
Check valve 1
5.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-56-01105
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.