← Backflow review queue

Backflow assembly test · Two Rivers Grill

Approved

Filed Sep 29, 2025 by Blake Okafor, Heritage Plumbing & Backflow · filed from phone

Report

Date of service
Sep 29, 2025
Assembly type
RP
Serial number
W967041
Size
1
Test gauge serial
G-1895
Gauge calibration date
Aug 2, 2024
Check valve 1
8.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
1.2 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-44-01037
  • RP relief valve must open at 2.0 psid or more.
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6536 Pine Knoll Dr
Owner: Harlow Holdings LLC
Parcel 001-44-01037