← Backflow review queue
Backflow assembly test · Corner Elementary School
ApprovedFiled Jan 13, 2025 by Morgan Fairley, Evergreen Backflow Testing · filed from phone
Report
- Date of service
- Jan 13, 2025
- Assembly type
- RP
- Serial number
- B569719
- Size
- 2
- Test gauge serial
- G-3374
- Gauge calibration date
- Jun 20, 2024
- Check valve 1
- 4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-79-01263
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
5630 Turkey Hill Way
Owner: Lindqvist Holdings LLC
Parcel 001-79-01263