Alachua County, FLCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 7593 Meadow Lark Trl

Approved

Filed Oct 30, 2026 by Jamie Wexler, Summit Backflow Testing · filed from phone

Report

Date of service
Oct 30, 2026
Assembly type
RP
Serial number
A583481
Size
3/4
Test gauge serial
G-8718
Gauge calibration date
May 11, 2026
Check valve 1
7.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-28-01056
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

7593 Meadow Lark Trl
Owner: Logan Benton
Parcel 001-28-01056