Backflow assembly test · 4550 Stone Gate Rd

Approved

Filed Feb 16, 2025 by Rowan Harlow, Evergreen Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Feb 16, 2025
Assembly type
PVB
Serial number
A454426
Size
1
Test gauge serial
G-3701
Gauge calibration date
Jan 8, 2025
Check valve 1
6.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-40-01283
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4550 Stone Gate Rd
Owner: Quinn Danner
Parcel 001-40-01283