Backflow assembly test · 7551 Quarry Ct

Approved

Filed May 15, 2025 by Reese Danner, Heritage Plumbing & Backflow · filed from phone

Report

Date of service
May 15, 2025
Assembly type
RP
Serial number
A690846
Size
3/4
Test gauge serial
G-5138
Gauge calibration date
Apr 17, 2024
Check valve 1
7.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
1.7 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-36-01268
  • RP relief valve must open at 2.0 psid or more.
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

7551 Quarry Ct
Owner: Alex Ellery
Parcel 001-36-01268