Backflow assembly test · Blue Heron Grill

Approved

Filed May 23, 2025 by Quinn Fairley, Lakeside Backflow Testing · filed from phone

Report

Date of service
May 23, 2025
Assembly type
RP
Serial number
K890881
Size
2
Test gauge serial
G-7217
Gauge calibration date
Jun 23, 2024
Check valve 1
3.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
1.1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 009-69-01160
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.