← Backflow review queue
Backflow assembly test · Maple Leaf Taqueria
ApprovedFiled Jan 13, 2026 by Sam Nguyen, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Jan 13, 2026
- Assembly type
- RP
- Serial number
- Z780536
- Size
- 2
- Test gauge serial
- G-9812
- Gauge calibration date
- Apr 7, 2025
- Check valve 1
- 3.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 009-23-01303
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
8789 Sycamore Dr
Owner: Kessler Holdings LLC
Parcel 009-23-01303