Backflow assembly test · Main Street Animal Hospital

Approved

Filed Jun 9, 2024 by Shawn Hollins, Keystone Backflow Testing · filed from phone

Report

Date of service
Jun 9, 2024
Assembly type
RP
Serial number
A409503
Size
2
Test gauge serial
G-6804
Gauge calibration date
Aug 15, 2023
Check valve 1
0.3 psid
Check valve 1 closed tight
No
Check valve 2
1.5 psid
Relief valve opened at
3.2 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 009-68-01000
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9458 Fox Run Dr
Owner: Okafor Holdings LLC
Parcel 009-68-01000