Brevard County, FLCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Main Street Self Storage

Approved

Filed Jun 7, 2024 by Sam Nguyen, Keystone Backflow Testing · filed from phone

Report

Date of service
Jun 7, 2024
Assembly type
RP
Serial number
A662753
Size
4
Test gauge serial
G-5244
Gauge calibration date
Sep 19, 2023
Check valve 1
3.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 009-23-01092
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

1386 Sycamore Trl
Owner: Calloway Holdings LLC
Parcel 009-23-01092