Backflow assembly test · Main Street Self Storage
ApprovedFiled May 31, 2025 by Shawn Hollins, Keystone Backflow Testing · filed from phone
Report
- Date of service
- May 31, 2025
- Assembly type
- RP
- Serial number
- A662753
- Size
- 4
- Test gauge serial
- G-6947
- Gauge calibration date
- May 15, 2024
- Check valve 1
- 0.5 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 3.5 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 009-23-01092
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
1386 Sycamore Trl
Owner: Calloway Holdings LLC
Parcel 009-23-01092