Brevard County, FLCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Crossroads Animal Hospital

Approved

Filed Aug 5, 2026 by Jordan Wexler, Lakeside Backflow Testing · filed from phone

Report

Date of service
Aug 5, 2026
Assembly type
RP
Serial number
Z564962
Size
1 1/2
Test gauge serial
G-7327
Gauge calibration date
Apr 17, 2026
Check valve 1
4.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 009-22-01112
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

1926 Spring Branch Ct
Owner: Wexler Holdings LLC
Parcel 009-22-01112