Brevard County, FLCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 8351 Cedar Hollow Trl

Approved

Filed Dec 14, 2024 by Shawn Kessler, Valley Plumbing & Backflow · filed from phone

Report

Date of service
Dec 14, 2024
Assembly type
RP
Serial number
B171269
Size
3/4
Test gauge serial
G-8253
Gauge calibration date
Aug 1, 2024
Check valve 1
5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 009-98-01188
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

8351 Cedar Hollow Trl
Owner: Jamie Whitcomb
Parcel 009-98-01188