Brevard County, FLCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 7250 Stone Gate Trl

Approved

Filed Aug 8, 2026 by Shawn Pruitt, Keystone Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Aug 8, 2026
Assembly type
DC
Serial number
B438024
Size
1
Test gauge serial
G-1418
Gauge calibration date
Aug 3, 2025
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 009-96-01085
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7250 Stone Gate Trl
Owner: Casey Ramirez
Parcel 009-96-01085