Brevard County, FLCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Apartments

Approved

Filed Mar 29, 2026 by Shawn Hollins, Keystone Backflow Testing · filed from phone

Report

Date of service
Mar 29, 2026
Assembly type
RP
Serial number
W584363
Size
1 1/2
Test gauge serial
G-2862
Gauge calibration date
Jul 27, 2025
Check valve 1
6.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 009-19-01145
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3670 Cedar Hollow Way
Owner: Nguyen Holdings LLC
Parcel 009-19-01145