← Backflow review queue
Backflow assembly test · 4225 Stone Gate Way
Needs reviewFiled Nov 24, 2026 by Sam Nguyen, Keystone Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Nov 24, 2026
- Assembly type
- RP
- Serial number
- B238727
- Size
- 1
- Test gauge serial
- G-5639
- Gauge calibration date
- Jan 1, 2026
- Check valve 1
- 7.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Relief valve opened at
- 1.4 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 009-20-01152
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Property
4225 Stone Gate Way
Owner: Avery Lindqvist
Parcel 009-20-01152