Brevard County, FLCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 8344 Laurel Ln

Approved

Filed Oct 30, 2024 by Sam Nguyen, Keystone Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Oct 30, 2024
Assembly type
RP
Serial number
W131536
Size
1
Test gauge serial
G-9036
Gauge calibration date
May 4, 2024
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Relief valve opened at
1.3 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 009-22-01021
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8344 Laurel Ln
Owner: Quinn Ellery
Parcel 009-22-01021