Backflow assembly test · Golden Self Storage
ApprovedFiled Oct 27, 2026 by Jordan Wexler, Lakeside Backflow Testing · filed from phone
Report
- Date of service
- Oct 27, 2026
- Assembly type
- RP
- Serial number
- K239060
- Size
- 1 1/2
- Test gauge serial
- G-6676
- Gauge calibration date
- Jun 15, 2025
- Check valve 1
- 0.7 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.1 psid
- Relief valve opened at
- 2.7 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 009-70-01270
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9192 Orchard Rd
Owner: Whitcomb Holdings LLC
Parcel 009-70-01270