Backflow assembly test · Hilltop Apartments
ApprovedFiled Aug 25, 2025 by Shawn Kessler, Valley Plumbing & Backflow · filed from phone
Report
- Date of service
- Aug 25, 2025
- Assembly type
- DC
- Serial number
- Z861950
- Size
- 1 1/2
- Test gauge serial
- G-3076
- Gauge calibration date
- May 3, 2025
- Check valve 1
- 5.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 009-75-01169
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
2997 Ridgeview Dr
Owner: Ramirez Holdings LLC
Parcel 009-75-01169